    The three major causes of refractometer trouble or failure in black liquor recovery boilers are:

    Loss of cooling water and its effect on the sensing head.

    Lack of reliability of the prism wash.

    Condensation in the sensing head.

    These may not apply to all refractometers due to differences in construction and circuitry.

    Cooling Water Loss

    It is of vital importance that the loss of cooling water be detected. This may be done through a temperature sensing element or flow monitor which shuts down the refractometer involved.

    Damage to the sensing element of a refractometer does not occur instantaneously, but it is essential that the system detect abnormal temperatures due to cooling water loss, flow blockage, etc., and that the cooling water be promptly restored.

    The individual refractometer manufacturer’s instruction and maintenance manuals shall be consulted with reference to: potential damage to the sensing element; identification of a damaged element; how and when to replace a damaged element.

    Prism Wash

    The time interval between prism washes may vary with the black liquor composition. It is recommended that the minimum wash period be 7-10 seconds of wash every 20 minutes. Short duration washes at more frequent intervals are more effective than long washes at long intervals. Ideally, steam pressure for prism washing should be 35 psig above the black liquor pressure, plus the pressure required to open the protective check valve.

    Awareness must be maintained of the effect of changes to the prism wash programming variables. Various refractometer systems have the capability to adjust: condensate drain time, steam on time, recovery time and interval between wash time. It may be possible to configure the system to have the total time that both refractometers are in their wash cycle represent a significant percentage of operating time. If one refractometer is out of service for repairs and the remaining refractometer is in prism wash, black liquor solids are not being monitored. Prism wash should be minimized to that needed to maintain the system.

    If high pressure steam is used, it may abrade the prism. If only high pressure steam is available, a reducing valve shall be used.

    The refractometer prism must have a clear polished optical surface, and if it becomes abraded, it must be replaced.

    If the prism wash system has not operated properly and the prism becomes coated, it must be removed and properly cleaned.

    Condensation in Sensing Head

    Condensate may build up in the refractometer sensing head and if this occurs, the instrument operation will be erratic.

    The procedure for determining this condition and for the elimination of excessive moisture in the sensing head is not the same for all refractometers. The manufacturer’s instruction and maintenance manuals shall be consulted and followed carefully.

    會員登錄

    X

    請輸入賬號

    請輸入密碼

    =

    請輸驗證碼

    收藏該商鋪

    X
    該信息已收藏!
    標簽:
    保存成功

    (空格分隔,最多3個,單個標簽最多10個字符)

    常用:

    提示

    X
    您的留言已提交成功!我們將在第一時間回復您~

    以上信息由企業自行提供,信息內容的真實性、準確性和合法性由相關企業負責,儀表網對此不承擔任何保證責任。

    溫馨提示:為規避購買風險,建議您在購買產品前務必確認供應商資質及產品質量。

    在線留言
    主站蜘蛛池模板: 日韩精品成人一区二区三区| 青青国产成人久久91网| 国产成人精品综合| 成人免费无码大片A毛片抽搐| 欧美xxxx成人免费网站| 成人精品一区二区三区中文字幕 | 国产成人精品免费视频大全五级| 国产成人精品怡红院在线观看| 亚洲国产成人手机在线电影bd| 激情成人综合网| 国产乱色精品成人免费视频| 欧美成人免费午夜影视| 在线观看免费成人| 欧美综合成人网| 亚洲成人福利网站| 成人午夜视频在线观看| 亚洲国产成人手机在线电影bd| 成人区人妻精品一区二区不卡网站 | 久久成人综合网| 成人免费乱码大片A毛片| 国产成人免费a在线资源| 日韩国产成人无码AV毛片| 亚洲成人网在线| 国产成人8X视频网站入口| 成人妇女免费播放久久久| 欧美成人片一区二区三区| 久久久久亚洲精品成人网小说| 国产成人福利精品视频| 国产精品成人一区二区三区| 成人精品一区二区三区中文字幕 | 成人动漫在线免费观看| 成人综合伊人五月婷久久| 成人网站在线进入爽爽爽| 69国产成人综合久久精品91| 亚洲欧洲国产成人精品| 四虎成人精品在永久在线观看| 国产成人影院在线观看| 国产成人精品午夜二三区| 国产成人免费永久播放视频平台| 国产成人精品无码播放| 国产成人av乱码在线观看|